Kestrel Home | Bulbs | Code Questions | Photo Gallery | Interesting Circuits |
NEW! Celebrity Endorsements |
Trusted Referrals |
Last update: 2011-05-24 Disclaimer:This table is meant to serve as a guideline for estimating purposes. Contact the Authority Having Jurisdiction, at the number provided, before performing work. |
Splicing Techniques for Aluminum Wire in Ventura County Residential Dwellings |
Contact for Authority Having Jurisdiction |
All UL Listed |
Ideal |
Leviton
|
Leviton
|
Leviton
|
King Innovation
|
Tyco |
City of San Buena Ventura |
805-654-7873 | No | Yes | No | Find out | Find out | Find out | Yes |
Oxnard |
805-385-7916 | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
Camarillo |
805-388-5395 | Find out | Find out | Find out | Find out | Find out | Find out | Find out |
Port Hueneme |
805-986-6515 | No | No | No | No | No | Yes | Yes |
Moorpark |
805-517-6272 | Find out | Find out | Find out | Find out | Find out | Find out | Find out |
Thousand Oaks |
805-449-2535 | No | No | Yes | Yes | Yes | Yes | Yes |
Ojai |
806-646-5581 press 3 | Find out | Find out | Find out | Find out | Find out | Find out | Find out |
Santa Paula |
805-933-4218 | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
Simi Valley |
805-583-6723 | Find out | Find out | Find out | Find out | Find out | Find out | Find out |
Fillmore |
805-574-7508 | Find out | Find out | Find out | Find out | Find out | Find out | Find out |
Piru |
805-654-2771 | Find out | Find out | Find out | Find out | Find out | Find out | Find out |
Back to Code Questions Index |
Jacuzzi Cheat SheetBack to Code Questions Index |
Motor Circuit SizingBack to Code Questions Index |
GFCI Used In Lieu Of GroundQuestion:Under what condition can a two-wire receptacle be replaced with a three-wire receptacle, when no ground is available in the box?Answer:[406.4(D)(2)(b)] A non–grounding-type receptacle(s) shall be permitted to be replaced with a ground-fault circuit interrupter type of receptacle(s). These receptacles shall be marked “No Equipment Ground.” An equipment grounding conductor shall not be connected from the ground-fault circuit interrupter type receptacle to any outlet supplied from the ground-fault circuit-interrupter receptacle. [406.4(D)(2)(c)] A non–grounding-type receptacle(s) shall be permitted to be replaced with a grounding-type receptacle(s) where supplied through a ground-fault circuit interrupter. Grounding-type receptacles supplied through the ground fault circuit interrupter shall be marked “GFCI Protected” and “No Equipment Ground.” An equipment grounding conductor shall not be connected between the grounding type receptacles. Note: GFCI protection functions properly on a 2-wire circuit without an equipment grounding (bonding) conductor, because the equipment grounding (bonding) conductor serves no role in the operation of the GFCI-protection device. CAUTION: The permission to replace nongrounding-type receptacles with GFCI-protected grounding-type receptacles doesn't apply to new receptacle outlets that extend from an existing ungrounded outlet box. Once you add a receptacle outlet (branch-circuit extension), the receptacle must be of the grounding (bonding) type and it must have its grounding terminal grounded (bonded) to an effective ground-fault current path in accordance with 250.130(C). Back to Code Questions Index |
3 Wire GroundGrounding Question for a 3-Wire Circuit:Which of the conditions below complies with NEC? Where is the NEC article that describes this? Answer: Drawing 1 is correct. Refer to NEC 250.122(C) Back to Code Questions Index |
Power To An Out BuildingQuestion: Can an outbuilding be powered by a subpanel in another outbuilding or must power come from the main service panel at the house?Answer: It is permissible to run a circuit from the sub-panel in the garage to the shed. It will require a disconnecting means (toggle switch is acceptable) in the shed in accordance with 225.31 and 225.32. Also take a look at 225.3 and its exception. A separate ground rod at the shed is not required because this is a single branch circuit and not a feeder. See 250.32(A) Back to Code Questions Index |
Power 2 Sheds From a Single Circuit?Question: Can this wiring scheme be used to omit a sub-panel and ground rod? The 240V receptacle powers a 9A compressor.Answer: Quit mucking around and just install a panel and ground rod(s) Back to Code Questions Index |
Splice in an Underground "T" Box or Fitting?Question: Can splices be made in an underground "T" box or fitting so that only 1 pipe needs to be brought up to the surface?Answer: No 314.29 p70-167: Boxes, Conduit Bodies, and Handhole Enclosures to be Accessible. Boxes, conduit bodies, and hand-hole enclosures shall be installed so that the wiring contained in them can be rendered accessible without removing any part of the building or, in underground circuits, without excavating sidewalks, paving, earth , or other substance that is to be used to establish the finished grade. Back to Code Questions Index |
Bathroom Wiring ConfigurationsQuestion: Can a circuit feeding a single bathroom and no other bathrooms also feed other non-bath rooms?Answer: No See 210.11(C)(3) Permissable configurations shown in drawing below Back to Code Questions Index |
230V Appliance WiringQuestion: New cloths dryer or cooking range has 4 wires but there are only 3 wires coming out of the wall.Answer: Refer to NEC Article 250.140 The 4 wire appliance can be connected to 3 outlet wires as per scenarios 3, 4 and 6 Back to Code Questions Index |
Kestrel Home | Bulbs | Code Questions | Photo Gallery | Interesting Circuits |
NEW! Celebrity Endorsements |
Trusted Referrals |